The 95M series modular, online UPS ranging from 40KVA to 500kVA is designed to protect any critical load for medium and largedata center achieving maximum availability. The 95M series feature the latest technology of 3-evel technology and PFC inputcontrol, which guarantees high efficiency of 96% and ultra-reliability. ts compact design ensures power density...
Specifications
| MODEL | 95M500/50X | 95M300/50X | 95M200/50X | 95M100/50X | 95M400/40X | 95M240/40X | 95M160/40 | X95M8040X | ||
|---|---|---|---|---|---|---|---|---|---|---|
| System Capacity | 500KVA | 300KA | 200KVA | 100KVA | 400KVA | 240KVA | 180KVA | 80KVA | ||
| Power Module Capacity | 50KVA45KW | 40KVA40KW | ||||||||
| lnput | Dual tnput | Standard Optional Standard Optional Standard | ||||||||
| Phase | 3 Phase+Neutral+Ground,380V/400V/415V(Eine-line) | |||||||||
| lnput Voltage Range | 304~478Vac (line-tine).full load; 228V-304Vac(tine-line).load decreases linearfly according to the min phase voltage | |||||||||
| Rate Frequency | 50/60Hz | |||||||||
| lnput Frequency Range | 40Hz~70Hz | |||||||||
| lnput PF | >0.99 | |||||||||
| Input THDi | <3%( 100% Linear load) | |||||||||
| Bypass | Rate Voltage | 380/400/415Vac (line-line) | ||||||||
| Rate Frequency | 50/60Hz | |||||||||
| Input Voltage Range | Seltable,-40%~+25% | |||||||||
| Bypass Frequency Range | Settable,±1Hz,±3Hz,±5Hz | |||||||||
| Bypass Overload | 110% long term cperation 130S for 5 mins 150% Tor imin >150% or 1s | 125% kong tem operaion 130 lor 10 mins 150%sor 1min >150% sor 300ms | 110% long term eparasian 125% for 5mins 150% lor 1min >150% for 1s | 125% bong term operaion 130% hor T0 mins 150% for 1 min >150% for 300ms | ||||||
| Output | Rate Voltage | 380/400/415Vac (line-line) | ||||||||
| Voltage Regulation | 1% for balanoe load; 1.5% for unbalance load | |||||||||
| Rate Frequency | 50/60Hz | |||||||||
| Frequency Precision | 0.1% | |||||||||
| Output PF | 0.9 | 1 | ||||||||
| Output THDu | <1%,Linear load;<5.5%,Non-linear load | |||||||||
| Crest Factor | 3:1 | |||||||||
| lnverter Overload | 110% for 1 hour;125% for 10 mins ;150% for 1 min; >150%for 200 ms | |||||||||
| Battery | Voltage | 士240Vdc | ||||||||
| Battery Number | 40pcs (Settable: even number from 32 to 44) | |||||||||
| Votlage Precision | ±1% | |||||||||
| Charge Power | up to 20% " Output active power | |||||||||
| Battery Cold Start | Standard Optional Standard Optional | |||||||||
| System | Effciency | AC Mode:95.0% ECO Mode: 99.0% Batlery Mode: 95.0% | ||||||||
| Display | 10.4" touch screen LCD +LED + keyboard | |||||||||
| IPClass | IP 20 | |||||||||
| lnterface | RS232,RS485,Programmable Dry Contact,USB | |||||||||
| Option | SNMP Card ,Parallel kt, SPD,LBS,Dust filter | |||||||||
| Temperature | Operation:~ 40 "℃ Storge: -40 ~ 70℃ | |||||||||
| Relative Humidity | 0~95% Non-condensing | |||||||||
| Alitude | <1000m.Within 100Om to 2000m, power derate 1% for every 100m rise | |||||||||
| Noise (1 meter) | 72dB@100% Ioad,89dB @ 45% load | |||||||||
| Applicable Standards | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | |||||||||
| Physical | weight (kg) | Cabinet | 450 | 220 | 170 | 120 | 450 | 220 | 170 | 120 |
| Power module | 45 | 4.4 | ||||||||
| Dimension W×D×H(mm) | Cabinet | 1300*1100 *2000 | 650*1095 *2000 | 650*960 *1600 | 600*980 *1150 | 1300*1100 -2000 | 650-10s5 *2000 | 650-960 *1600 | 600*980 *1150 | |
| Power module | 510*700"178 | |||||||||